Electrochemical cell
Self cleaning
Flow adjustment
Wetted parts are of PVC and PMMA
pH electrode by insertion, permanently or not
PRINCIPLE
Those cells are designed for the survey or regulation of Chlorine in swimming pool or chlorination process. Water and process characteristics for measurement:
Free of oil and grease.
Constant pH between 6.5 and 8 pH.
Constant Temperature with a maximum of 40°C.
Constant Conductivity.
The reaction cell includes a Cu/Pt pair of electrodes. It delivers an electric current, proportional to the concentration of free active chlorine and then amplified by a transmitter. This basic measurement guarantees a high accuracy and perfect reproducibility. The electrodes are permanently cleaned with a continuous movement of small glass balls. The sampled water circulation creates the glass balls movement, adjustable with the integrated regulation valve.
SPECIFICATIONS
Principle: electrochemical cell Electrodes: copper/ platinum Accuracy: 0,001 ppm Self cleaning action: glass balls Required flow: 35 l/h - integrated valve Pressure inlet: maximum 5 bar Pressure outlet: atmospheric Wetted parts: PVC, PMMA, FPM Process connections: PVC nozzle, diam. 12/14 mm Mass: 1 kg (without fittings) Electric output: cable, 5 wires 0.22 mm2, connector
General Catalog 192-01 08/11/2018 10:15
Free active chlorine monitoring assembly BAMOCHLOR 192
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France