This converter (input s.i., output non s.i.) with galvanic insulation allows powering of measuring loop or conversion of analogue signal from a transmitter (passive or active) installed in an hazardous area.
TECHNICAL FEATURES
Measuring loop
:
1
Main power
:
230 V AC ±10 % / 48 ... 62 Hz
(indicator of powered unit)
by a green LED on front board)
Consumption
:
≤ 2.7 W
Mounting
:
In safe area
Input: s.i. - Output not s.i.
Loop powered
For transmitter, 2 wires, active or passive
:
≥ 15 V DC with current of 21 mA
Input signal
from hazardous area
:
0/4-20 mA
Output signal
In and to safe area
:
0/4-20 mA
Input impedance
Current
:
50 Ω ±2 %
Voltage
:
> 2 MΩ
Load resistance
Current
:
≤ 800 W
Voltage
≥ 10 kW
Drifts
Voltage powering
:
≤ ±0.01 % / % Ualim
Output resistance
:
≤ ±0.01 % / 100 Ω
Temperature influence
:
≤ 150 ppm / °C
Response time
:
≤ 350 ms
Galvanic insulation between
Input / Output / Supply
:
2500 V AC / 50 Hz
Installation
:
In safe area
Case
:
In ABS
Mass
:
200 g
Storage temperature
:
-25 ... +70 °C
Operating temperature
:
-20 ... +60 °C
% R. H.
:
5 ... 95 % (without condensing)
Connectors
:
Plug-in, clamp terminals
Fitting
:
Rail acc. EN 50022
General Catalog 235-01 12/11/2018 17:27
Intrinsic safety converter BXNT
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France