Designed for overfill and leakage sensors MAXITOP and MAXIMAT®
DESCRIPTION
This power supply and alarm signal relay SHR CS (DIN rail mounting) isspecially designed for the new MAXIMAT leakage and overfill transmittersand liquid filling of pipes sensors CAPSYTRON SFL. It is useful with theprevious range MAXIMAT SU... and VK. It assures a continuous survey of the measurement loop, a LED indicatesthe circuit status. The alarm signal drives 2 output relays to control 2 separates systemssuch as a horn and a flashing light.
TECHNICAL FEATURES
Supply power: 230 V ±10%, 50/60 Hz or 24 V DC ±10% Power consumption: about 3 VA / 3 W Ambient temperature: -20 to +60°C Housing: 22.5 x 75 x 110 mm, IP 40 for standard rail per DIN EN 50 022 (35 x 7.5 mm top-hat rail)Terminals:Screw terminals, IP 20 maximum wire cross-section 2.5 mm2
Relay outputs: 2 floating changeover contacts, maximum 250 V (50/60 Hz) 3 A, or 115 V DC, 0.5 A Minimum load: 10 mA at 5V DC
Indicators: green LED operation green LED relay pulled in red LED overfill/leakage alarm red LED interrupted circuit red LED short-circuit
Delay time: release delay adjustable from 0.3 to 3 sec
Measuring circuit: 12 V DC maximum, short circuit 110 mA maximum inductance <5 mH maximum capacitance < 0.5 μF maximum
Measuring cable: 300 m maximum, wire cross-section 0.5 mm2 minimum
CE mark: in accordance with low-voltage directive (2006/95/EG), EMC directive (89/336/CEE) and standards EN 50 082-2: 1995, EN 55 011 (class A) 1998, EN 610010-1 1993
DIBT approval: Z-65.11-122, Z-65.13-265, Z-65.13-294,Z-65.40-201 and Z-65.40-272 for leakage and overfill detection.
General Catalog 555-06 17/04/2018 11:22
Measuring transducer MAXIMAT®SHR CS
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France