For aggressive and non electrically conductive liquids
Positive active alarm
Auto diagnostic system and LED indication when in use with a SHR C transducer
Approvals: DIBT Z-65.40-272, for leakage detection, WHG §19 when in use with a SHR C.. transducer
APPLICATIONS
The MAXIMAT is ideal for permanently survey risks of leakage of a liquidfrom a storage tanks, filling equipment, dosing pumps etc. Convenient touse with non-electrically conductive liquids, oils, emulsified, non-flammable,water endangering liquids. It is a perfect instrument to detect fluid in adouble wall tank. MAXIMAT LW VK operates with liquids of specific weight from 0.7 g/cm3
PRINCIPLE
The sensor MAXIMAT LW VK is designed to detect conductive liquidsnon-electrically conductive. The detection results from the position of amagnet inside the float and a Reed contact inside the probe. It isnecessary to use it with a SHR C transducer.The liquids may not generate deposit originating jamming of float.
TECHNICAL FEATURES
Main power supply: 24 V DC ±10%; caution: DC current circuit should be protected by a fuse of 250 mA
Power consumption: Approx. 3 W
Ambient temperature: -20 to +60°C
Operating pressure: Atmospheric, 0.8 to 1.1 bar
PROBE
Material: PE-HD
Cable: TPK, 2 x 0.5 mm2, shielded
Hysteresis: About 2 mm
Terminal housing: PBT, fibre glass reinforced, IP 65 acc. EN 60 529
Terminals: Screw connectors, IP 20; max. wire cross-section 2.5 mm2
Output: To a transducer MAXIMAT SHR C..
Cable length 300 m maximum,
wire cross section 0.5mm2 as a minimum
CE mark: In accordance with low-voltage directive (2006/95/CE) and EMC directives (2004/108/EG)
Approvals: DIBT Z-65.40-272, for leakage detection
General Catalog 555-08 17/04/2018 11:23
Leakage detection sensor MAXIMAT®LW VK
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France