Dedicated probes and sensors With Factor probe C= 0.01, 0.1, 1 and 10
2 adjustable analog output 0/4-20 mA, galvanic insulated
3 relay outputs (NO contact)
Wall mounting IP 65
DESCRIPTION
BAMO Mesures SAS designed the resistivity metre 319 ML / DB for process control and survey of demineralised water through two bottles of resins.
Input 1: controls the first bottle, as a blind instrument (without display) As soon as the fluid resistivity is less than the preset value the relay 1 switches a signal alarm to inform the operator.
Input 2: controls the second bottle with its own alarm parameters. The measurement of resistivity is permanently displayed.
3 relay outputs are to be used either for the input 1 or input 2; adjustments are done by the operator.
The 4-20 mA outputs allow the report of process operations, in order to have a true image of water quality.
TECHNICAL FEATURES
Displayed parameters: Measurement values - Configuration Menu Display: Back lighted - 1 line of 16 alphanumerical characters ; 9,2 mm high Indication: LED alarms status Configuration: 8 push buttons keyboard on front face - Keyword protected Scales: 200 Ω .cm to 200 MΩ .cm Accuracy: ± 0,3% Probe input: Coaxial connector BNC type Input 1: 20 MΩ .cm Input 2: adjustable
Temperature compensation: On range 20 MΩ, automatic with an input for a 3 wires Pt 100 Ω /0° Manually from 0 to 100°C
CAUTION: with 0.1 sensor Factor there is no automatic compensation (manual only) Relay outputs: 3 closing contacts (Silver alloy), voltage free
Thresholds: 3 programmable independent thresholds - with adjustable hysteresis 0…100% - and adjustable timer from 0 to 9999 sec
Output relay (S4): Not available
Contact: Initial resistance 100 mΩ as a maximum (voltage drop 6 V DC 1 A) Rated at 831 V AC / 3 A / 277 V AC ; 90 W / 3 A / 30 V DC Switching capacity (minimum) 100 mA, 5 V DC (depending of switching frequency, ambient conditions, accuracy) Mechanical life time (minimum) 5 x106 operations (180 commutation/min) Electrical life time (minimum) 2 x105 (20 comm./min) [3 A, 125 V AC], [3 A, 30 V DC] and 105 (evaluated charge) for 3 A, 125 V AC
Calibration sequence: Relay outputs inhibited, analogical outputs stand on last values Measurement output: 0/4-20 mA (maxi 600 Ω) proportional to measurement, galvanic insulated Program Testing: Simulation through the menu on measurement and relays outputs Main power supply: 230 V AC / 50-60 Hz [other on request] - Consumption 10 VA Models: Wall mounting, IP65, cable glands, connections on screw terminal
OPTION
Data Logger: Cycle average measurement record, with a programmable period, 150000 records maxi on MMC (multi media card) / External driver necessary
General Catalog 319-02 17/04/2018 10:49
Resistivy meter BAMOPHOX 319 ML-DB
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France