• Power supply: 21.6 to 253 V AC 50/60 Hz and 19.2 to 300 V DC
• 4 digits Display / LED 14 segments
• Power supply to sensor: 15 to 25 V DC ; 0/4-20 mA
• Housing 48 x 96 mm
• Protection: Front IP 65
• Outputs: 2 relays or 2 relays + 1 analogue output 0/4-20 mA
DESCRIPTION
The both versatile and programmable displays are convenient for local control of process where ambient conditions are severe and humid.
ITU 402 includes 2 relays, SPDT.
ITU 412 includes 2 SPDT relays plus 1 analogue output 0/4-20 mA.
The 4 digits display LED of 13.8 mm high / 14 segments, has a resolution from 1999 to 9999 with a floating decimal point; it shows as well the relay status (ON/OFF) of each.
All parameters are setup through the front keyboard.
A multi language help file is available through the menu.
Both displays are supplied on request already set up
During the start up, a test for simulation may be run on each relay without a real input signal.
Both indicators provide a simple programming routine.
These IP65 indicators are of a DIN 43700 cutout: 48 x 96 mm, to fit in industrial cabinets.
TECHNICAL FEATURES
Power supply
:
21.6 to 253 V AC 50/60 Hz and 19.2 to 300 V DC
Power consumption
:
3.5 W max.
Inputs
:
Current: -1 to 25 mA,
Voltage: -20 mV to 12 V DC
RTD (Pt 100. Ni 100) and resistor
TC (Types B, E, J, K, L, N, R, S, T, U, W3, W5 & LR)
Operating temperature
:
-20 to +60 °C
Outputs
:
2 Relays SPDT, 230 V AC
Analogue: 0/4-20 mA, 800 Ω max
Power to sensor
:
15 to 25 V DC / 0 to 20 mA
Case
:
DIN 43700, IP65, black polycarbonate, 230 g
Mass
:
230 g
Electric connections
:
Fast coupling connectors (no screws)
Agreements
:
Conformity to directives EMC 2004/108/CE,EN 61326-1,
DBT 2006/95/CE, EN 61010-1
General Catalog 222-03 27/11/2018 18:36
Panel mounting indicators ITU 402 - ITU 412
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France