Zone 0 ATEX certified (Zone 2 for the alarm device location)
Solar powered or standard electric battery
Energy saving mode adjustable (control frequency adjustable from 6 min up to 9 days)
3 inputs, for any NIVOIL probes
Automatic recognition of type probe
3 relay outputs with audible alarm
DESCRIPTION
Designed for the monitoring of hydrocarbon fluids separators, the alarm device NIVOIL® may be connected to 1, 2 or 3 sensors.
Hydrocarbon layer thickness sensor to detect when the maximum thickness is reached.
Overfill sensor to detect when the fluids are on the highest level.
Sludge layer sensor for alarming when maintenance is necessary.
The 3 sensors may be connected to any input of the alarm device NIVOIL. Any combination of the sensors can be wired. The instrument recognizes automatically the sensor type. A LED indicates the sensor type on the diagram on the front board. The alarm device NIVOIL has a built-in buzzer; it is possible to disable its function.
Low power consumption This model working with a 10 to 27 V DC power supply has low energy consumption. It is designed for the use of a solar powered battery or any standard electric battery (consumption is 0.1 W – 12 V DC – with 3 sensors connected with one complete control cycle per hour).
Sleep mode This mode is adjustable by modifying the frequency of control cycle (from 6 minutes up to 9 days). A continuous control mode could be switched on when there is no limit on consumption.
ATEX certified All the components are ATEX certified. The sensors are for a location in zone 0 and the alarm device corresponds to a zone 2.
TECHNICAL FEATURES
NivOiL® CU/12 – Alarm device
Main power supply: 10...27 V DC Power consumption: 0.1 W / 12 V DC (3 sensors connected and 1 control cycle per hour) Housing protection: IP65, according EN 60529 Temperature limits: -20...+60°C
Sensor inputs: 3 inputs with automatic sensor type detection for hydrocarbon fluids layer thickness, overfill level, sludge layer level
Monitoring: The alarm device NIVOIL has an auto-diagnostic of measuring loop An alarm signal occurs in case of dysfunction due to a short circuit or a broken cable.
Display and signals: 1 function signal LED (green) on each channel 1 alarm signal LED (red) on each channel Built-in audible alarm, disabled by DIP switch configuration
Front panel: 2 push buttons for diagnostic test and alarm clearance Outputs: 3 relay outputs, Power switch 250 V AC as a maximum / 3A, Potential free change over contacts ATEX Certificate: BVS 10 ATEX E 011 / The alarm device may be mounted in Ex area, zone 2
Ex protection class: Ex II 3 (1) G Ex nAC [ia Ga] IIB / IIA T4 Gc (Intrinsic safety) CE Marks According to EC directives (72/23/EEC), Low Voltage Guidelines: RL 2006/95/EG & RL93/68/EWG,
EMV Guidelines: RL 89/336/EWG (EN 61326) ATEX RL 94/9/EG (ATEX 95) EN 60079-0 (General requirements) - EN 60079-11 (Intrinsic safety) - EN 60079-26 (Group II; category 1G)
NivOiL® -OP/10 – Hydrocarbon fluid layer thickness sensor (Only for use with an alarm device NIVOIL)
Sensor type: Capacitive, high frequency Wetted parts: Antistatic PE stem; Stainless steel end probe
Cable: Elastomer resistant to oils and hydrocarbon fluids, blue colour; wires 2x 1mm2, connections to the alarm device NIVOIL on screw connectors; 10 m long cable (other lengths on request - maximal length is 300 m)
Protection: IP68 acc. EN 60529 Temperature limits: -20...+60°C ATEX certificate: BVS 07 ATEX E 091 X / This sensor is suitable for location in zone 0 Ex protection class:Ex II 1 G Ex ia IIB T4 (Intrinsic safety)
NivOiL® -HPS/10 – Overfilling sensor (Only for use with an alarm device NIVOIL)
Sensor type: Ultrasonic detection type Wetted parts: PVC; Elastomer cable
Cable: Elastomer resistant to oils and hydrocarbon fluids, blue colour; wires 2x 1mm2, wiring on screw connectors; 10 m long cable (other lengths on request - maximal length is 300 m)
Protection: IP68 acc. EN 60529 Temperature limits: -20...+60°C ATEX certificate: BVS 09 ATEX E 021 X / This sensor is suitable for location in zone 0 Ex protection class:Ex II 1 G Ex ia IIB T4 (Intrinsic safety)
NivOiL-SP/10 – Sludge layer sensor (Only for use with an alarm device NIVOIL)
Sensor type: Ultrasonic detection type Wetted parts: PVC; Elastomer cable
Cable: Elastomer resistant to oils and hydrocarbon fluids, blue colour; wires 2x 1mm2, wiring on screw connectors; 10 m long cable (other lengths on request - maximal length is 300 m)
Protection: IP68 acc. EN 60529 Temperature limits: -20...+60°C ATEX certificate: BVS 09 ATEX E 021 X / This sensor is suitable for location in zone 0 Ex protection class:Ex II 1 G Ex ia IIB T4 (Intrinsic safety)
General Catalog 531-02 23/04/2018 11:04
Alarm system for oil-water separator NivOil® / 12 V DC