Warning! You are consulting an archived documentation:
This product is not anymore manufactured or marketed by BAMO
Do not hesitate to contact us if you are looking for a substitution product certified or if you have a question
AUTO-CLEANING SENSOR by reverse polarity
LCD back lighted display, friendly using menu
1 specific input for CCK sensor
1 analog output 0/4-20 mA
Automatic temperature compensation
2 relays for ON/OFF and PID regulation
Pulse output for ON-OFF, PID regulation
1 alarm relay with timer
1 input for flow controller
RS 485 interface
DESCRIPTION
The DCW 100 monitor is designed for measuring and regulation in disinfection process (chlorine, chlorine dioxide, ozone) and in particular for CCK sensors. The auto-cleaning system ASR (patented) maintains automatically the sensor operational. The cleaning is an electrochemical operation. The DCW 100 applies a suitable potential between the electrodes to produce oxygen and hydrogen without reagents addition. The gases eliminate the existing deposits. The cleaning sequence is finished in 30 seconds and may be done twice a day. During the cleaning, the status is displayed; the regulation is set on stand-by. Through the friendly using menu, an easy configuration is done on regulation, thresholds, temperature compensation and alarm events. With the back lighted display it is easy to read perfectly the measure and temperature at anytime. The analogical output is galvanic insulated, and configured on various scales.
TECHNICAL FEATURES
Display: Measurement – temperature – relays status – configuration menu back lighted LCD display, 2 lines Configuration: Front keypad, 5 keys – Protected access through a key code Temperature compensation: Manual or Automatic (Pt 100 Ω at 0°C sensor input) Automatic cleaning: With the sensor type CCK only (auto-recognition)
Analogical inputs: 1 for CCK sensor 1 for temperature (Pt 100 Ω at 0°C sensor)
Flow controller input: For PNP inductive flow controller (NO status) – NO or NC configuration Adjustable thresholds: 2 independents thresholds – adjustable as increasing or decreasing adjustable hysteresis
Alarm: 1 system dysfunction alarm, common to: – Too long injection (adjustable timer from 0 to 90 minutes) – Thresholds overriding – Automatic cleaning
Switching power: 6 A / 250 V, max. 550 VA (resistive load) with load resistor protection Pulse regulationAdjustable cycle from 2 to 99 s (pulses + pause)
Pulse length: 0.1 to 9.9 s Delay: 2 to 99 s
Impulse frequency: 100 to 7200 pulses / hour Proportional regulation P range XP, adjustable within the measuring range,
Integral time TN: 0 - 2000 s Output signal: 0/4 - 20 mA (max. load 500 Ω) , galvanic insulated Serial interface: RS 485 (9600 bauds), 8 bits Ambient temperature: 0...+50°C Storage: -20...+65°C Humidity: Max. 90 % RH at 40°C no, condensing Model: Wall mounting, IP 65 housing in ABS, connections on screw terminal Power supply: 230 V, 40-60 Hz / 10 VA – internal fuse 63 mA Turn on delay: 0 to 200 s
CE Marks According to EC directives
General Catalog 194-05 08/11/2018 10:18
Monitor for CCK sensors DOSAControl DCW 100
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France