MAXITOP is ideal to detect the presence of a liquid on floors due to a leakage. With its fail safe detection loop, it is permanently operational.
PRINCIPLE
MAXITOP LWC-B is designed to detect conductive liquids with a reactance up to 5 kOhm/cm and a coupling capacitance towards ground of more than 50 pF. The liquids may not generate electrical insulating or conductive deposit.
MAXITOP LWC-B has 5 different types of connection:
• Low voltage output 50 V AC/DC max.; 0.5 A max.; 10 VA max.
• Output relay to CST unit (data sheet 555-09)
• Output relay to SHR unit (data sheet 555-06)
• Direct connection to PLC
• Signalization with TC4 and TC1 unit (data sheet 555-07 and 10)
TECHNICAL FEATURES
Power supply: 15...26 V DC
Power consumption: Approx. 1 W
Ambient temperature: -20...+60° C
Housing: In PBT, protection (acc. EN 60 529)
Cable: Standard length 6, PVC sheathed, 5x0.5 mm², shielded
Detection: Minimal height of fluid of 1 mm
CE mark: In accordance with low-voltage directive (2006/95/CE) and EMC directives (89/336/CEE)
General Catalog 556-05 17/04/2018 11:26
Leakage detection sensor MAXITOP – LWC-B
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France