CP4
CP4
Total chlorine sensor
CP4


Complete system (Assembly sold separately)
• Water treatment, drinkable quality and sea-water
• Surfactants: partial tolerance
• Low incidence of pH changes
• Operating temperature 45 °C max.
• Operating pressure 3 bar max.
APPLICATIONS

Water treatment (drinkable quality water and sea water)

TECHNICAL FEATURES
Measuring parameters : Total chlorine (Free + combined chlorine)
Chlorinating agents
:
Inorganic compounds additives: NaOCl; Ca(OCL)₂;
gaseous chlorine; chlorine produced by electrolysis
Surfactants: partial tolerance
Measuring system : Closed cell with 3 electrodes and electrolyte
Output signal
:
4 ... 20mA, 2-wire, screw connectors (2 x 1mm²)
No galvanic insulation
Operating temperature
:
1 ... 45 °C
Automatic temperature compensation
Operating pressure
:
0.5 bar max. (without securing collar)
3 bar (with securing collar)
No vibrations, no pulsating flow
Flow rate : About 30 l/h
Supply voltage : 12 ... 30 V DC; Load: 500 to 900 Ω
pH operating range : pH 4 to pH 12 (low incidence of pH)
Conductivity : From 10 μS/cm up to 50 mS/cm (sea-water)
Interferences : Incidence of ClO₂ and O₃ on measuring signa
Zero adjustment : Not necessary (from factory)
Slope calibration : Through 1 point (slope), with BAMOPHAR 194 (DPD 4)
Materials : PVC-U; PEEK, AISI 316 Ti
Dimensions : O.D. 25mm, length 220mm (4-20mA model)

 

CE Conformity: The instrument meets the legal requirements of the current European Directives
CODE NUMBERS AND REFERENCES
Code Reference Measuring range Resolution
193 047 CP4.MA2 0.005 ... 2 mg /l 0.001 mg /l
193 048 CP4.MA5 0.01 ... 5 mg /l 0.01 mg /l
193 049 CP4.M10 0.01 ... 10 mg /l 0.01 mg /l
Replacements
193 915 M48.4E Sensor end with diaphragm (not for sea-water)
193 xxx M48.4S Sensor end with diaphragm for sea-water
193 964 ECP1.4/GEL Electrolyte for sea-water

 

Other versions on request (measuring range, power supply, output signal, connector, etc.)
 
Precautions
Flow rate must be constant and a measuring cell with flow controller is necessary (see data-sheet 193-95).
For an easy commissioning and operations, we propose assemblies designed for specific applications.
General Catalog 193-08
12/11/2018 15:23
Total chlorine sensor
CP4
Technical & Commercial support's main contacts
Ask a QUOTATION online
BAMO Mesures SAS
22, Rue de la Voie des Bans
Parc d'activités de la Gare
95100 ARGENTEUIL France
Tel: +33 1 30 25 83 20
Fax: +33 1 34 10 16 05
E-mail: export@bamo.fr
URL: http://www.bamo.fr
Siret: 314 055 864 000 65
TVA Intra: FR 08 314 055 864
APE: 2651 B
Capital: 400 000 Euros
Built by CARIMEDIA since 1998