Temperature linear measure with resistance sensor, Pt 100, Pt 1000, Ni 100. Resistance conversion to a standard 4-20mA signal (RTM). With ohmic input, it is possible to make a 60 points linearization from customer specification (specially for RTM) To avoid lost or modification of data, in case of power outage, calibration data are saved in a EEPROM. T2F5333 is delivered with configuration required by the final user. programmation on site is done by the Loop Link 5905 kit (page 601/6)
CHARACTERISTICS
Power supply: non EEx: 8,0 ... 35 V EEx: 8,0 ...28 V
Internal consumption: 25 mW ... 0,8 W Probe currant: > 0,2 mA, < 0,4 mA Accuracy: ± 0.3% Power outage: 8 Vdc Respose time: from 0.33 to 60 s Temperature factor: < ± 0.01 % EC / °C Linearity error: < 0.1 % EC
Power supply effect: < 0.005 % EC / Vdc Line resistance
Factor (RDT): ± 0.01°C / ambiant T° CEM data immunity effect: < ± 0.5 % EC Temp calibration: 24°C ± 4°C Input max difference: 50% of max value Tightness (box/terminal): IP68 / IP00 Wires max section: 1 x 1.5 mm2 Max. line resistance (per wire): 10 Ω Weight: 50 g
EC = Calibrated scale
General Catalog 601-01 17/04/2018 11:37
Programmable 2 wires transmitter T2FR 5333