Capacitive, high frequency, fail-safe detection
For aggressive and conductive liquids
Two sensors- Positive active alarm
Auto diagnostic system and LED indicator
WHG §19 approval: DIBt-No.: Z-65.40-316
APPLICATIONS
With its integrated transmitter and connection for diagnostic, the MAXIMAT isideal to detect the presence of a liquid in a double wall pipe, catch basins,catch spaces...
PRINCIPLE
The transmitter MAXIMAT is designed to detect the presence of electricallyconductive liquids with a reactance up to 5 kΩ/cm and a couplingcapacitance towards ground of more than 50 pF. The liquids may notgenerate electrical insulating or conductive deposit. The MAXIMAT has 3 different outputs, factory built-in:
• Binary output to active optocoupler, numeric input • Analog 0...20 mA output for any analog input of PLC
TECHNICAL SPECIFICATIONS
Main power supply: 15 ... 26 V DC; caution: DC current circuit should be protected by a fuse of 250 mA. Power consumption: approx. 3 W Ambient temperature: -20 to +60°C Operating pressure: atmospheric, 0.8 to 1.1 bar Terminal housing: PBT, fibre glass reinforced, IP 65 acc. EN 60 529 Terminals: screw connectors, IP 20; max. wire cross section 2.5 mm2
Outputs: • Switch [+DO / -DO]:optocoupler NPN, maximum 30 mA • Switch [+AO / -AO]:current 0...20 mAConfiguration: with 4 DIP switches
Lighting signal: 1 LED inside the terminal housing for correct operating system
CE mark: in accordance with low-voltage directive (73/23/CEE)and EMC directives (89/336/CEE)and standards EN 50 082-2: 1995,EN 55 011 (class A): 1998
DIBTApproval: Z-65.40-316, for leakage detection, WHG§19