Warning! You are consulting an archived documentation:
This product is not anymore manufactured or marketed by BAMO
Do not hesitate to contact us if you are looking for a substitution product certified or if you have a question
Floor standing leakage detector
Capacitive, high frequency, fail-safe detection
For aggressive and electrically conductiveliquids
Positive active alarm
Auto diagnostic system and LED indicator
APPLICATIONS
With its integrated transmitter and connection for diagnostic, the MAXIMAT isideal to detect the presence of a liquid due to a leakage of dangerous andnon-flammable liquids in computer rooms, barrel warehouse catch basins.
PRINCIPE
The transmitter MAXIMAT is designed to detect conductive liquids with areactance up to 5 kΩ/cm and a coupling capacitance towards ground ofmore than 50 pF. The liquids may not generate electrical insulating orconductive deposit. The MAXIMAT has 3 different outputs, factory built-in:
• Binary output to active optocoupler, numeric input • Analog 0...20 mA output for any analog input of PLC
TECHNICAL SPECIFICATIONS
Main power supply: 15 ... 26 V DC; caution: DC current circuit should be protected by a fuse of 250 mA. Power consumption: approx. 3 W Ambient temperature: -20 to +60°C Operating pressure: atmospheric, 0.8 to 1.1 bar
Outputs: • Switch [+DO / -DO]:optocoupler NPN, maximum 30 mA • Switch [+AO / -AO]:current 0...20 mA
Configuration: with 4 DIP switchesLighting signal: 1 LED inside the terminal housing for correct operating system
CE mark: in accordance with low-voltage directive (73/23/CEE)and EMC directives (89/336/CEE)and standards EN 50 082-2: 1995,EN 55 011 (class A): 1998 DIBTApproval: Z-65.40-316, for leakage detection, WHG§19
General Catalog 555-05 17/04/2018 15:49
Leakage detection sensor MAXIMAT®LWC-B
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France