With its integrated positive safety converter, the MAXITOP is ideal to give an alarm before the overfilling of a tank. Convenient to use with any electrically conductive, non-flammable liquids; even highly aggressive liquids.
PRINCIPLE
The detector MAXITOP is designed to detect conductive liquids with a reactance up to 5 kOhm and a coupling capacitance towards ground of more than 50 pF. The liquids may not generate electrical insulating or conductive deposit.
The MAXITOP has 4 different possible transmissions: • Low voltage output (max. 50 V ac/dc, max. 0.5 A, max. 10 VA) • Relay output in use with a CST device (data sheet 555-09) • Direct connection to a PLC • Direct connection to an alarming unit TC4 (data sheet 555-07)
TECHNICAL FEATURES
Main power supply: 15...27 V DC
Power consumption: < 1 W
Ambient temperature: -20...+60 °C
Operating pressure: atmospheric (0.8 to 1.1 bar)
Stem: PE
Process connection: 2" G, PVC, sliding – adjustable immersion depth
Lengths (L): 500, 700, 900 mm (other lenghts on request)
Terminal housing: PBT, fibre glass reinforced, IP 65 acc. EN 60 529
Terminals: Screw connectors, IP 20, max. wire cross-section 2.5 mm2
Input: For an external button switch in order to run a test sequence
Signalling display: 1 LED (green) inside the terminal housing
Output: Reed contact, potential free, for low voltage, max. 50 V AC/DC, max. 0.5 A, max. 10 VA
CE mark: In accordance with low-voltage directive (2006/95/CE) and EMC directives (89/336/CE)
General Catalog 556-01 17/04/2018 11:25
Compact Overfill Sensor MAXITOP
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France