With its integrated positive safety converter, the MAXITOP is ideal to give an alarm when a leakage occurs in a double wall tank or retention basin. Convenient to use with any electrically conductive, non-flammable liquids, even highly aggressive liquids.
PRINCIPLE
The probe MAXITOP LW C is designed to detect conductive liquids with a reactance up to 5 kOhm/cm and a coupling capacitance towards ground of more than 50 pF. The liquids may not generate electrical insulating or conductive deposit.
The MAXIMAT LW C has 4 different possible transmissions:
• Low voltage output (max. 50 V ac/dc, max. 0.5 A, max. 10 VA) • Relay output in use with a CST device (data sheet 555-09) • Direct connection to a PLC • Direct connection to an alarming unit TC4 (data sheet 555-07)
TECHNICAL FEATURES
Main power supply: 15 ... 27 V DC Power consumption: < 1 W Ambient temperature: -20 to +60 °C Operating pressure: Atmospheric / Limits, 0.8 to 1.1 bar Stem: PEHD, Ø 40 mm Cable: 6 m long as a standard, PVC, shielded, 5 x 0.34 mm2 Terminal housing: PBT, fibre glass reinforced, IP 65 acc. EN 60529
Terminals: Screw connectors, IP 20, max. wire cross-section 2.5 mm2
Switching point: 5 mm submerged end of stem as a minimum Hysteresis: 2 mm approx. Signal: 1 LED (green) inside the terminal housing CE mark: in accordance with low-voltage directive (2006/95/CE) and EMC directives (2004/10/EG)
General Catalog 556-03 17/04/2018 11:25
Leakage detection probe MAXITOP – LW C
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France