Available in PVC-PPH, PPH, PVDF and stainless steel 316 L
1 or 2 bi-stable change over contacts
Small dimensions
Lightly sensitive to specific weight variations
4-20 mA continuous transmitter (option RTM MNR6)
APPLICATIONS
Pumps and solenoid valves ON/OFF automation, low and high alarm signal, automatic tank filling up or draining, in all industries. MNR6 series are suitable only for non viscous and non sticky liquids, without magnetic and/or solid particles. The liquids may not crystallize.
PRINCIPLE
Switches are mounted in the guiding stem; they are actuated by the magnet, built in the float, to allow 1 or 2 level detections to correspond with your application.
PRESENTATION
All wetted parts are in PVC with PA (float), PPH, PVDF or stainless steel 316L (see the cross table). Mounting on the tank is through a threaded connector or with a flange; a different type without connection (straight stem) is available with a cable output. In all models the float is easily removed by unscrewing the lower blocking ring.
TECHNICAL FEATURES
Max pressure (at 20°C): 3 bar for composite material 20 bar for stainless steel
Temperature limits: PVC, +5 to +50°C PPH, -5 to +105°C PVDF, -10 to +110°C 316L, -20 to +110°C
Contact (1 or 2): Change over contacts, bi-stable by using a stopper Switching capacity: 60 VA
Minimum distances: 100 mm between 2 contacts Upper dead zone = 60 mm Lower dead zone = 50 mm
Precision: ± 2 mm Hysteresis: 8 mm
WIRING
Wiring is through the screw terminal in the head housing. For remote cable connection, the cable output model allows the use of 1 bi-stable change over contact or 2 bi-stable contacts NO or NC or NO and NC. The DIN connector model is only available with 1 contact.
General Catalog 551-01 17/04/2018 11:21
Magnetic float level controller MNR 6
BAMO Mesures SAS
22, Rue de la Voie des Bans Parc d'activités de la Gare
95100 ARGENTEUIL France